CMC 156 EP: 3 Phase Voltage + 3 Phase Current Test Set
Voltage generators/-amplifiers
Setting range
3-phase AC (L-N) 3 x 0 ... 127.5 V
1-phase AC (L-L) 1 x 0 ... 255 V
DC (L-N) 3 x 0 ... ±127.5 V
Power
3-phase AC (L-N) 3 x 50 VA at 127.5 V
1-phase AC (L-N) 1 x 100 VA at 127.5 V
1-phase AC (L-L) 1 x 140 VA at 255 V
DC (L-N) 1 x 90 W at ±127.5 V
75
1 4 0
1 2 7 . 5
255
Output voltage / V
0
1-phase AC (L-L)
3-phase AC (L-N)
1-phase AC (L-N)
Output power / VA
Accuracy
2
error < 0.015 % rd.
3
+ 0.005 % rg.
3
typ.
at 0 ... 127.5 V
error < 0.04 % rd. + 0.01 % rg. guar.
at 0 ... 127.5 V
Distortion (THD+N)
4
< 0.015 % typ., < 0.05 % guar.
Resolution 6 mV
Connection 4 mm (0.16 in) banana sockets/comb. socket
Current generators/-amplifiers
Setting range
3-phase AC (L-N) 3 x 0 ... 12.5 A
1-phase AC (3L-N) 1 x 0 ... 27 A
DC (3L-N) 1 x 0 ... ±30 A
Power
3-phase AC (L-N) 3 x 40 VA at 12.5 A
1-phase AC (3L-N) 1 x 75 VA at 27 A
1-phase AC (L-L) 1 x 75 VA at 12.5 A
DC (3L-N) 1 x 60 W at ±12.5 A
75
1 4 0
1 2 7 . 5
255
Output voltage / V
0
1-phase AC (L-L)
3-phase AC (L-N)
1-phase AC (L-N)
Output power / VA
Accuracy
5
error < 0.015 % rd. + 0.005 % rg. typ.
at 0 ... 12.5 A
error < 0.04 % rd. + 0.01 % rg. guar.
at 0 ... 12.5 A
Distortion (THD+N)
4
< 0.025 % typ., < 0.05 % guar.
Ranges 1.25 A / 12.5 A
Resolution (for respective range) 50 µA / 500 µA
Resolution 500 µA
Max. compliance voltage (L-N)/(L-L) 4 VRMS, 6 Vpk / 8 VRMS, 12 Vpk
Connection 4 mm (0.16 in) banana sockets/comb. socket
At only 9.8 kg / 22 lbs, the CMC 156 EP is the smallest and lightest solution for three-phase
testing of numerical relays. Its high precision makes it also the perfect device (class 0.05 %
Working Standard) for testing and calibrating meters, transducers and other measurement
equipment.
Generators, general
Frequency
range sine signals 10 ... 1000 Hz
range transient signals DC ... 3.1 kHz
accuracy/-drift ±0.5 ppm / ±1 ppm
resolution 5 µHz
Phase
angle range - 360° ... +360°
resolution 0.00
error at 50/60 Hz < 0.005° typ., < 0.02° guar.
Bandwidth (-3dB) 3.1 kHz
Simulated
power S, P
(calibration of
energy meters)
accuracy
6
error < 0.05 % rd.
3
typ., < 0.1 % rd. guar.
at 10-63 Hz, 50 ... 127.5 V, and 0.1 ... 12.5 A
temperature drift 0.001 % / °C typ.. < 0.05 % / °C guar.
Low level outputs
Setting range 6 x 0 ... 5 VRMS
Max. output current 2 mA
Accuracy error < 0.025 % typ., < 0.1 % guar.
Resolution 250 µV
Distortion (THD+N)
4
< 0.015 % typ., < 0.05 % guar.
Unconventional CT/VT simulation linear
Isolation SELV
Usability completely independent from internal
amplifier outputs
Connection 16 pin combination socket (rear side)
Binary Inputs
Number 10
Trigger criteria Toggling of potential-free contacts or DC
voltage compared to threshold voltage
Input characteristics 0 ... +250 VDC threshold or potential-free
Ranges (in RMS values) 250 VDC
Resolution of threshold 1.5 V
Sample rate 10 kHz (resolution 100 µs)
Time stamping accuracy ±0.00015 % of rd.
3
±70 µs
Max. measuring time infinite
Counting function < 3 kHz at pulse width > 150 µs
Galvanic isolation 2 galvanically isolated groups (4 + 6)
Max. input voltage 250 VDC
Connection 4 mm (0.16 in) banana sockets or measure-
ment combination socket
Counter inputs 100 kHz
Number 2
Max. counting frequency 100 kHz
Pulse width > 3 µs
Threshold voltage 6 V
Voltage hysteresis 2 V
Max. input voltage ±30 V
Isolation SELV
Connection 16 pin combination socket (rear side)
Technical Data
1
CMC 156 EP
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - CMC 156 EP

CMC 156 EP: 3 Phase Voltage + 3 Phase Current Test SetVoltage generators/-amplifiersSetting range3-phase AC (L-N) 3 x 0 ... 127.5 V1-phase AC (L-L) 1

Pagina 2

Ordering InformationCMC 156 EP with Test Universe SoftwareVE001616 CMC 156 EP BasicVE001617 CMC 156 EP ProtectionVE001618 CMC 156 EP Advanced Protecti

Comentarios a estos manuales

Sin comentarios